4 Mechanical Installation WirelessHART Fieldgate SWG70
18 Endress+Hauser
4.2.3 Connecting a remote antenna
WARNING!
• Outdoor installations can be subject to lightning strikes. Install a surge arrestor, to protect the
installation against transients or damage caused by lightning strikes.
NOTE!
Tension relief and bending radii: Ensure sufficient relief of tension on the cables during
installation and note the minimum bending radii of the cables.
The antenna must be connected to the Fieldgate SWG70 by means of coaxial cable. A surge arrestor
provides protection against lightening strikes. The surge arrestor must be installed directly on the
Fieldgate SWA70 antenna connection. Install the components according to Fig. 4-6.
Fig. 4-6: Installation of an remote antenna
1 Before installing the remote antenna, make sure that the Fieldgate has been disconnected from
line power
2 Install the components according to Fig. 4-6
3 Install the surge arrestor in a way that all indoor connections are protected
4 Connect the surge arrestor to protective grounding
5 Install the remote antenna where it is within the antenna range of other WirelessHART
devices, see Chapter 4.1.5
1 Omnidirectional antenna 5 Surge arrestor,/4, without mechanical fixing
2 Directional antenna 6 RF coaxial cable with connectors
3 Coaxial adaptor 7 Coaxial adaptor
4 RF coaxial cable with connectors 8 Fieldgate SWG70
2
1
7
8
64 53